AES-1 (Aerosol
Sensor Unit)
|
-
Particulates of
0.5 microns or larger can be monitored.
-
The aerosol
sensor unit can be used to keep optimum driving
of filtering equipment related to a clean room
depending on actual condition of cleanliness
level.
|
FEATURES
-
Stable
and sensitive detection for Particulates of 0.5
microns and larger can be monitored.
-
Unique
air sampling method using "heater" to generate
updraft, preventing choked flow. Suction pump
is not necessary.
-
Long life
laser. 20,000 h
-
Compact
size and low cost.
APPLICATIONS
Clean booth, Fan Filter Unit, Clean Unit etc Clean
Room related filtration system.
SPECIFICATION
|
Light Source
|
Semiconductor Laser
|
Life (Light Source)
|
20,000 h
|
Detection Method
|
Light Scattering
|
Air Sampling Method
|
Using "Heater" to generate updraft. Approx 0.1 L/m.
|
Min. Detectable Size
|
0.5 µ
|
Detection Range
|
100 ~ 100,000 pcs / 1 cf
|
Operating Condition
|
0 °C ± 40 °C 30 %RH ~ 80 %RH
|
Output
|
1 kHz Pulse Output
|
Power Consumption
|
300 mA
|
Input Voltage
|
DC12 V ± 10 %
|
Dimension
|
90 x 90 x 23 mm
|
Weight
|
Approx 120 g
|
|
AES-1000 (Aerosol
Monitor)
|
The Aerosol Monitor which has easy-to-read display,
and link to Ethernet system, can materialize
simplified monitoring of Particulates at multiple
location.
|
FEATURES
-
Stable
and sensitive detection for Particulates of 0.5
microns and larger. Easy-to-read air
cleanliness level, equivalent of ISO5 / Class
100 - ISO8 / Class 100,000.
-
Unique
air sampling method using "heater" to generate
updraft, preventing choked flow. Suction pump
is not necessary.
-
Alarm
comes on when the setting level goes beyond the
required cleanliness, while monitor gives alarm
signal output.
-
Link to
Ethernet system with purpose of monitoring at
multiple location.
-
Long life
laser. 20,000 h
-
Compact
and light, easy installation. Low cost
|
APPLICATIONS
Any place where you need
simplified cleanliness level monitoring
DISPLAY
SPECIFICATION
Display
|
10 x LED lights shows equivalent of Class 100 ~ Class
100,000
100(ISO5)-1,000(ISO6)-2,000-3,000-5,000-10,000(ISO7)-20,000-30,000-50,000-100,000(ISO8)
|
Detection
method
|
Light Scattering
|
Sensor
|
Shinyei AES-1 Aerosol Sensor
|
Min.
detectable size
|
0.5 µ
|
Air Sampling
method
|
Updraft airflow generated by built-in heater enables
air sampling of approx. 0.26 gal per minutes
|
Cleanliness
Class
|
From level of equiv. of ISO5 / Class 100 ~ ISO8 /
Class 100,000
|
Alarm
Display
|
Alarm LED light comes on when reaching to setting
level
|
Alarm
Output
|
TTL open collector output in sync with alarm display
|
Interface
|
Ethernet x 1 port
|
Power
Supply
|
DC12 V ± 10 % 500 mA
|
Operating
Temp/Humidity
|
0 °C ~ 40 °C 30 %RH ~ 80 %RH
|
|